DSpace Repository

Method Validation for Analysis of Aroclor 1260 in Transformer Oil using Gas Chromatography-Electron Capture Detection

Show simple item record

dc.contributor.author Jeevanantham, J.J.
dc.contributor.author Dissanayake, D.A.T.W.K.
dc.contributor.author Liyanaarachchi, G.V.V.
dc.contributor.author Mubarak, M.N.A.
dc.contributor.author Wijesinghe, W.M.A.K.
dc.contributor.author Wijegunasekara, J.K.A.B.
dc.date.accessioned 2019-01-11T04:19:05Z
dc.date.available 2019-01-11T04:19:05Z
dc.date.issued 2018-11
dc.identifier.citation Jeevanantham, J.J. (2018). "Method Validation for Analysis of Aroclor 1260 in Transformer Oil using Gas Chromatography-Electron Capture Detection", Proceedings of the 23rd International Forestry and Environment Symposium 2018 of the Department of Forestry and Environmental Science, University of Sri Jayewardenepura, Citrus Waskaduwa, Waskaduwa, Sri Lanka, 65 p. en_US
dc.identifier.issn 2235-9427
dc.identifier.uri http://dr.lib.sjp.ac.lk/handle/123456789/8166
dc.description.abstract Polychlorinated Biphenyls (PCBs) are a group of synthetic aromatic compounds which has been used as thermal insulators and coolants in transformers, capacitors, motors and hydraulic systems due to the high thermal capacity and also as stabilizers in the paint industry. The number and the location of chlorine atoms in a PCB molecule determine many of its physical and chemical properties. Despite its applications, PCBs are considered as persistent organic pollutants (POPs) and they have been identified as carcinogenic to human and classified under the group 1 by the International Agency for Research on Cancer (IARC). This study presents the validation data of the method developed for analysis of Aroclor 1260 in transformer oils. The transformer oil samples were prepared according to the ASTM D 4059 with few modifications and analyzed by Gas Chromatography–Electron Capture Detection (GC-ECD) using HP 5 GC column (30 mx0.32 mm x0.25 μm) with a temperature programme starting from 100o C to 300o ̊C at a rate of 15o C min-1. The PCBs in transformer oils were extracted to 2,2,4-Trimethylpentane followed by deactivated florisil cleanup. The study was performed under matrix matched condition to eliminate the matrix effect that was found to be significant. The method was found linear over a wide working range from 2.5-100 ppm and the linearity of the method was 0.994 with a lower limit of determination of 2.5 ppm. The method shows satisfactory repeatability with relative standard deviation below 7% over the entire working range. Accuracy of the method was assured using spike recoveries at 5 ppm, 10 ppm and 50 ppm with 85%, 105% and 93% respectively. The selectivity of Aroclor 1260 was confirmed against Aroclor 1254 and Aroclor 1242 considering uniquely identified non – overlapping chromatographic peaks with reference to the standard reference materials (SRMs). Based on the performance characteristics, this method can be suggested as an accurate and precise methodology to analyze Aroclor 1260 present in transformer oil. en_US
dc.language.iso en en_US
dc.publisher University of Sri Jayewardenepura 2018 en_US
dc.subject PCB, Gas chromatography-electron capture detection, Aroclor 1260, Transformer oil en_US
dc.title Method Validation for Analysis of Aroclor 1260 in Transformer Oil using Gas Chromatography-Electron Capture Detection en_US
dc.type Article en_US


Files in this item

This item appears in the following Collection(s)

Show simple item record